400200 CSA 6
  
Delivery Information
Gas Controls must be fitted by a Gas Safe registered Engineer

UK Order value of less than £30.00 (Excluding VAT) £5.50
UK Order value more than £30.00 (Excluding VAT) FREE

1 Ireland, (Inc Northern Ireland) Belgium, Luxembourg,
Netherlands, France, Germany £16.00

2 Austria, Denmark, Finland, Hungary, Italy, Poland,
Portugal, Slovakia, Spain, Sweden,Turkey £19.50

Whilst Pactrol Controls Ltd (Pactrol Solutions.com) makes every effort to keep the information on this web site accurate, we make no warranty or representation, express or implied about its accuracy, completeness or appropriateness for a
particular purpose. Thus you assume full responsibility for using the information
at this web site, and you understand and agree that neither
Pactrol Controls Ltd (Pactrol Solutions.com) nor any of its employees is responsible or liable for any claim, loss or damage resulting from its use.

400200 CSA 6
Price
£160.00 Inc VAT : £192.00
Quantity
Sorry, this item is out of stock. Please contact our sales line or use Live Chat for availability
Product Description

Compact, low-cost, fully automatic control for atmospheric and small forced-draught burners. Tested and approved by BG plc to meet GAD requirements.

Description

The Pactrol CSA provides automatic ignition control and flame supervision for gas burners with direct inputs of up to 60kW (forced-draught), or above (atmospheric). It is suitable for use with either direct main-burner ignition or pilot-burner ignition systems.

The control provides a short pre-purge period followed by an ignition period, and there is a choice of alternative timings. Flame supervision is by flame rectification, with the option of ultra-violet sensing with the addition of a special UV head. The control will shut-down and provide volatile lock-out following flame-failure or an unsuccessful ignition attempt, and may be reset by interrupting the electrical supply.

Time switches, thermostats, etc., are normally arranged to switch the electrical supply to the control.

Controlling the main-burner only, with a pilot left on for long periods, is not recommended.

The control will provide an extended pre-purge at reduced main voltage, and will shut-down if this drops below 150v. A supply surge voltage arrester is fitted.

Construction

IP40 housing, dimensions, 100 x 95 x 63 mm